What is cooling water treatment?
Cooling water treatment keeps cooling towers, heat exchangers and closed loops free of scale, corrosion, fouling and microbiological growth. As water evaporates in a tower, dissolved salts concentrate and warm, aerated water favours bacteria, including Legionella.
A programme combines a scale and corrosion inhibitor, an oxidising biocide, often a non-oxidising biocide and a biodispersant. Products are formulated blends with their own SDS.
Where is cooling water treatment used?
Cooling chemicals are used in open evaporative towers and closed loops in refineries and petrochemical plants, power plants, mining and metals plants, food and beverage factories in FMCG, HVAC systems of large buildings and data centres.
How are cooling chemicals produced?
Cooling chemicals are formulated from standard actives.
- Inhibitors blend phosphonates (HEDP, PBTC), polymers, orthophosphate or zinc, and azoles (tolyltriazole, benzotriazole) for copper.
- Oxidising biocides include sodium hypochlorite, stabilised bromine and chlorine dioxide.
- Non-oxidising biocides include isothiazolinones, DBNPA, glutaraldehyde and quaternary ammonium compounds.
- Each lot is tested for active content, pH, density and appearance.
Cooling water product types
The table compares the main product types; each is then explained with its typical uses. The programme is designed from make-up water analysis and system metallurgy.
| Scale & corrosion inhibitor | Oxidising biocide | Non-oxidising biocide | Closed-loop inhibitor | |
|---|---|---|---|---|
| Chemistry | Phosphonate, polymer, azole, zinc | Hypochlorite, bromine, ClO₂ | Isothiazolinone, DBNPA, glutaraldehyde | Nitrite, molybdate, azole |
| Dosing | Continuous, by bleed-off | Continuous or slug | Slug, 1–2 times a week | Initial fill and top-up |
| Control | Product residual, LSI | Free halogen residual | Microbial counts | Inhibitor residual |
| Best for | Open towers | Routine microbial control | Biofilm and resistant bacteria | Chilled and hot-water loops |
Scale and corrosion inhibitors
Allow higher cycles of concentration without scale while protecting steel and copper. See our antiscalants.
- Open recirculating cooling towers
- Heat exchangers on river or well water
- Evaporative condensers
Oxidising biocides
Kill bacteria and algae quickly and keep a measurable residual; hypochlorite is the most common.
- Continuous microbial control
- Legionella risk management
- Large refinery and power towers
Non-oxidising biocides and biodispersants
Penetrate biofilm and control organisms that tolerate halogens; biodispersants loosen deposits.
- Biofilm and slime control
- Systems with organic contamination
- Rotation with oxidising biocide
Closed-loop inhibitors
High-dose inhibitors for sealed systems with little water loss.
- Chilled-water and hot-water loops
- Engine and process cooling jackets
- Data-centre cooling loops
Typical product properties
| Parameter | Scale & corrosion inhibitor | Non-oxidising biocide |
|---|---|---|
| Appearance | Clear, colourless to amber liquid | Clear to pale liquid |
| pH (neat) | per product, acidic or neutral | about 2–7 |
| Density (20 °C) | about 1.1–1.3 g/cm³ | about 1.0–1.1 g/cm³ |
| Freezing point | about −10 °C | per product |
| Active content | per TDS | per TDS (e.g. 1.5 % or 14 % isothiazolinone) |
Each product has its own TDS. The binding specification is the one in our offer and in the Certificate of Analysis for each lot.
Water quality targets
| Parameter | Typical guide (open tower) |
|---|---|
| Cycles of concentration | about 3–6, higher with good treatment |
| pH | about 7.5–8.8 |
| Free chlorine (if used) | about 0.2–1.0 mg/L |
| Total bacteria (dip slide) | below about 10⁴ CFU/mL |
| Corrosion rate (carbon steel) | below about 3 mpy (0.075 mm/year) |
How the chemistry works
Programmes are monitored with coupons, dip slides and routine water tests. Legionella risk should be managed under guidance such as ASHRAE 188 or national codes.
- Phosphonates and polymers hold calcium salts in solution and disperse particles.
- Azoles form a film on copper and stop it plating out on steel.
- Oxidising biocides react fast but are consumed by organics and ammonia; non-oxidising biocides act more slowly and penetrate biofilm.
- Biocides are toxic to aquatic life (H400, H410); some are corrosive (H314) or skin sensitisers (H317).
Cooling water applications
Refinery and petrochemical towers
Large towers combine inhibitor, chlorine or bromine and periodic non-oxidising biocide; hydrocarbon leaks are monitored.
Power plants
Condenser cooling uses inhibitors and oxidising biocide; some plants use sulphuric acid for pH and alkalinity control.
Industry and food plants
Process cooling and compressors are protected with inhibitor and biocide programmes.
HVAC and data centres
Towers and closed loops need strict Legionella control and corrosion protection.
Closed loops
Nitrite or molybdate with azoles protect sealed chilled- and hot-water systems for long periods.
Main cooling chemical supplier countries
Cooling chemicals are formulated by water-treatment companies worldwide; key actives come from China (phosphonates), Europe and the United States (biocides and polymers). Biocides must be registered where they are used, for example under the EU Biocidal Products Regulation (product type 11).
Cooling tower treatment in Turkey
Turkey’s industry, power plants, hotels, hospitals and data centres use cooling towers, served by international and local water-treatment companies; biocides need local registration.
Mercafons supplies inhibitors, biocides and closed-loop products through its Istanbul office, with programme advice and CoA for each lot.
Cooling tower chemical price
The cooling tower chemical price is best compared as total programme cost per month, which depends on tower size, make-up water quality and cycles. Request a quote with your water analysis.
Cooling chemical packaging
Packages carry product name, lot number, net weight and hazard labels.



Shipment
Some inhibitors and many biocides are dangerous goods, often Class 8 or Class 9 (environmentally hazardous); classification is on each SDS. A 20 ft container holds about 18–20 t. See logistics. HS code: 3824.99 (biocides may fall under 3808.94).
Storage and safety
Storage
Keep products in closed containers, out of sun and frost, in a bunded area. Store oxidising biocides apart from acids, organics and other biocides.
Safety
Wear goggles, chemical gloves and protective clothing; use respiratory protection when handling concentrated biocides. Never mix products in the same tank.
Cooling water treatment FAQ
How many cycles of concentration can I run?
It depends on make-up water and treatment; most towers run 3–6 cycles. Our engineers can calculate the limit.
Why use two different biocides?
Alternating oxidising and non-oxidising biocides controls more organisms and limits resistance.
How is Legionella controlled?
By a risk assessment, continuous biocide residual, regular cleaning and Legionella testing.
Can I use antiscalant alone?
Usually no; open towers also need corrosion and microbial control.
What is a closed-loop inhibitor?
A high-dose inhibitor for sealed systems, such as nitrite or molybdate with azole.
Cooling chemical documents: MSDS, TDS and CoA by type
Each cooling product has its own SDS and TDS; biocides also carry registration details. See technical documents.